F-Gas English Low GWP
Minden kérdés
HFC | Flammable | CO₂ | NH₃
Könnyű kérdések |
Közepes nehézségű kérdések |
Nehéz kérdések
1
Könnyű
What is the base unit of mass according to the International System of Units (Système International d’Unités)?
| t |
| Pound |
| kg |
| N |
2
Közepes
What process takes place in the condenser of a refrigeration system?
| The medium flowing through the evaporator (glycol, water) condenses, whilst the refrigerant evaporates. |
| In the condenser, the refrigerant releases the heat absorbed in the evaporator into the surroundings. |
| Hot refrigerant vapour is pumped from the compressor to the condenser, where it is cooled and then condensed. In this heat exchanger, the resulting liquid refrigerant is also slightly subcooled. |
| The refrigerant releases the heat absorbed in the compressor via the condenser |
3
Közepes
What determines the condensation temperature of an air-cooled unit?
| On the ambient temperature. |
| On the evaporation (boiling) temperature. |
| On the superheat temperature. |
| On the compressor and discharge temperatures |
4
Közepes
Is energy required when heat is transferred from the condenser to the surroundings?
| The heat flow balances the energy input. |
| Yes, in every case. |
| No, because according to the second law of thermodynamics, thermal energy always flows from a body at a higher temperature to a body at a lower temperature. |
| Yes, but only when using HFC refrigerants. |
5
Közepes
What should you pay attention to during the operation of the condenser?
| Pay attention to the fan’s operation and the ambient temperature. |
| Care should be taken to ensure that the air temperature at the condenser inlet is lower than the air temperature at the condenser outlet. |
| Ensure that the air temperature at the condenser outlet is higher than the condensation temperature. |
| You should ensure the general maintenance of the condenser and keep the heat exchange surfaces clean. |
6
Közepes
What criteria should be considered when selecting a suitable condenser?
| The required capacity of the condenser and the technical specifications declared by the manufacturer must be taken into account. |
| These include size and the number of fans. The geometric parameters of the condenser must be taken into account. |
| First and foremost, you should consider the operating noise level of the fans, the diameter of the connection pipes and the colour scheme. |
| Condensers should be selected based on your own experience, and the condenser’s geometric parameters should be taken into account. |
7
Közepes
How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?
| Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure. |
| Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency. |
| Contaminants increase the heat transfer area and reduce the condensing pressure. |
| Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers. |
8
Közepes
If an air-cooled condenser becomes contaminated, will the condensation efficiency?
| It will increase. |
| It remains unchanged. |
| It will increase as a result of the fan speed being raised further. |
| It will decrease. |
9
Közepes
What can cause frost to form on the evaporator?
| An increase in refrigerant flow resistance and a reduction in the refrigerant flow rate through the evaporator. |
| Frost build-up on the evaporator increases airflow resistance and, consequently, causes the fan motor to work harder. |
| a drop in cooling capacity. |
| A reduction in the temperature of the cooled substance. |
10
Közepes
What happens when the evaporation temperature drops?
| The compressor’s cooling capacity decreases. |
| The condenser fan speed increases. |
| The discharge temperature decreases. |
| The compressor’s cooling capacity increases. |
11
Közepes
When is defrosting using the refrigerant possible?
| In the case of air-cooled chillers, only when the air temperature is above 0°C. |
| Never. We use electricity for defrosting (for example, using a special electric heater). |
| Only when using speed-controlled fans. |
| Defrosting using the refrigerant is not possible at all. |
12
Közepes
When can frost form on the evaporator surface?
| Frost always forms on air coolers. |
| Only in the case of air coolers, when the air temperature drops below 0°C. |
| In the case of finned evaporators. |
| Frost forms only when the refrigeration system is operating continuously. |
13
Közepes
In the case of extensive pipework systems, secondary evaporation of the refrigerant can be prevented by...
| using smaller-diameter pipes. |
| by insulating the pipes between the compressor and the condenser. |
| using larger-diameter pipes. |
| additional cooling. |
14
Közepes
How does hot gas defrosting of the evaporator work?
| We switch on the gas heater directed at the evaporator. |
| We swap the outlet and inlet sides of the evaporator. |
| This involves reversing the direction of rotation of the compressor. |
| Heated vapour (hot gas) from the compressor is directed into the evaporator piping. |
15
Közepes
What is the function of the evaporator in a refrigeration system?
| It evaporates the water flowing through the evaporator. |
| Thanks to the evaporator, the cooled medium transfers heat to the boiling refrigerant. |
| It ensures that the refrigerant is superheated over the largest possible heat exchange surface area. |
| It cools the refrigerant. |
16
Közepes
What conditions must be met for the evaporator to be defrosted using electric heaters?
| Thanks to the forced air flow created by the fans, the heat from the heaters is transferred to the heat exchanger. |
| The electric heaters must be positioned beneath the evaporator’s heat exchange surface. |
| The electric heaters must be in contact with the evaporator’s heat exchange surface (the heater must touch the fins). |
| The electric heaters must be positioned in direct contact with the refrigerant so that the refrigerant flowing through the evaporator is at a sufficiently high temperature. |
17
Közepes
Refrigerant distributor:
| acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded. |
| ensures an even distribution of the refrigerant to the individual sections of the evaporator. |
| ensures even distribution of the refrigerant to the individual sections of the condenser. |
| ensures the even distribution of the refrigerant discharged by compressors connected in parallel. |
18
Közepes
What are the possible methods of defrosting air coolers?
| Natural defrosting; there are no other effective methods. |
| Electric defrosting only. |
| Electric defrosting, liquid defrosting or defrosting using hot refrigerant vapour. |
| Hot gas defrosting. |
19
Közepes
The boiling point increases (and consequently the rate of evaporation increases) if the pressure above the liquid...
| Rises. |
| It behaves differently depending on the ambient temperature. |
| Remains constant. |
| Falls. |
20
Közepes
MOP in thermostatic expansion valves stands for:
| maximum operating pressure. |
| self-cleaning of the valve in the event of moisture in the refrigerant freezing. |
| maximum pressure switch protection. |
| minimum flow opening. |
21
Közepes
The function of a thermostatic expansion valve (TEV) in a refrigeration system is:
| to maintain a constant suction pressure to the compressor. |
| to consistently adjust the evaporation pressure in the condenser depending on the temperature of the refrigerant vapour leaving the condenser. |
| to control the amount of refrigerant supplied to the evaporator depending on the superheat of the vapour leaving that heat exchanger. |
| regulating the superheat of the refrigerant leaving the evaporator so that it is at the minimum value. |
22
Közepes
When using a capillary tube, what type of motor can be used in the compressor?
| An electronically commutated motor approved for use with the compressor should be used. |
| A low-speed motor should be used. |
| A motor with low starting torque can be used. |
| A motor with high starting torque must be used. |
23
Közepes
What does the thermostatic expansion valve regulate?
| Discharge temperature. |
| The mass flow of the refrigerant injected into the evaporator. |
| Cooling. |
| Evaporation pressure after. |
24
Közepes
The refrigerant absorbs heat when...
| it evaporates. |
| sublimates |
| freezes. |
| it condenses. |
25
Közepes
In the case of a thermostatic expansion valve, the manufacturer specifies...
| ...the degree to which the valve is filled with refrigerant liquid. |
| …the degree of refrigerant expansion. |
| ...the superheat value during valve operation. |
| ...the static superheat of the valve. |
26
Közepes
How do we charge a new or repaired system with refrigerant when it is fitted with an expansion valve
| Charging with refrigerant takes place during operation via the outlet connection of the refrigerant capillary tube. |
| to the suction side of the compressor. |
| in any way. |
| behind the condenser to the liquid refrigerant receiver. |
27
Közepes
What does a thermostatic/electronic expansion valve regulate?
| The number of revolutions of the compressor per unit of time. |
| The evaporation pressure, closing when it falls below the setpoint temperature. |
| Condenser subcooling by adjusting the condensing pressure. |
| The amount of refrigerant by controlling the evaporator superheat. |
28
Közepes
What does the MOP function in expansion valves mean?
| This means that these expansion valves are set to limit subcooling. |
| This means that these expansion valves are set to a specific suction pressure. |
| It means that these expansion valves are set to limit the maximum operating pressure. |
| This means that these expansion valves are set to prevent overheating. |
29
Közepes
The lower the temperature of the liquid refrigerant upstream of the expansion valve,
| ...the lower the theoretical coefficient of refrigeration efficiency qo will be, and the lower the refrigeration capacity Qo will be. |
| ...the lower the theoretical coefficient of cooling efficiency qo will be, whilst the cooling capacity Qo remains unchanged. |
| ... the higher the theoretical coefficient of cooling capacity qo will be, and the greater the cooling capacity Qo will be. |
| ...the lower the theoretical coefficient of cooling efficiency qo will be, and the lower the system’s energy efficiency will be. |
30
Közepes
The MOP point in the expansion valve, due to the maximum evaporation temperature of the refrigeration system, ...
| The value of the MOP point is irrelevant. |
| ...must be approximately 7 K lower. |
| ...must be approximately 5 K lower. |
| ...must be approximately 7 K higher. |
31
Közepes
What is the function of the suction pressure regulator?
| To maintain the suction pressure at the highest possible level. |
| It maintains the suction pressure at a constant level. |
| It limits the suction pressure and protects the compressor from excessively high suction pressure. |
| It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system. |
32
Közepes
What is the function of the valve regulating water flow through the condenser?
| To maintain the condensing pressure at the highest possible level. |
| To maintain the condensing pressure at a constant level. |
| To maintain the condensing pressure at the lowest possible level. |
| To maintain the water temperature at the highest level. |
33
Közepes
The use of a refrigerant distributor requires a thermostatic expansion valve …
| … with external pressure equalisation. |
| … with an adsorption-type sensor filling. |
| … with a MOP function. |
| … with internal pressure equalisation. |
34
Közepes
What properties should good insulation materials have?
| It must be able to absorb large amounts of moisture. |
| It must have a good antistatic coating |
| It must have a high thermal conductivity. |
| It must have a low thermal conductivity. |
35
Közepes
When do we encounter the superheated state?
| It is a condition in which the compressor motor temperature rises excessively. |
| This is the temperature difference between the actual vapour temperature and the vapour temperature at saturation. |
| This is a state that arises as a result of the temperature difference between the suction side and the discharge side of a compressor. |
| It is the temperature difference between the evaporation temperature and the ambient temperature. |
36
Közepes
How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?
| We are unable to check this. |
| We check using a pressure gauge fitted on the discharge side of the compressor. |
| We check this using a sight glass. |
| We check using a liquid pressure gauge. |
37
Közepes
The liquid lines are located...
| between the condenser and the liquid receiver. |
| between the evaporator and the regenerative heat exchanger. |
| between the compressor and the condenser. |
| between the evaporator and the compressor. |
38
Közepes
What is the function of the liquid receiver in a refrigeration system?
| The tank is used to store and ensure an adequate supply of refrigerant in the event of fluctuations in the thermal load of the refrigeration system. |
| When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system. |
| The tank is used to collect the liquid refrigerant and excess oil in the system. |
| The reservoir is used to further cool the liquefied refrigerant leaving the condenser. |
39
Közepes
What is the purpose of the liquid refrigerant reservoir?
| When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system. |
| The tank is required during maintenance work, when there is a temporary need to store the refrigerant that has been circulating in the refrigeration system up to that point. |
| The tank is used to collect the liquid refrigerant and excess oil in the system. |
| The tank is used to further cool the liquefied refrigerant leaving the condenser. |
40
Közepes
Where should the liquid receiver be installed?
| It should be fitted between the compressor and the condenser. |
| It should be fitted just before the compressor. |
| It should be installed downstream of the condenser, upstream of the expansion valve. |
| It should be fitted after the evaporator. |
41
Közepes
What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?
| It opens when the suction pressure upstream of the compressor drops. |
| It closes when the suction pressure upstream of the compressor drops. |
| It regulates the condensing pressure. |
| It regulates the evaporation pressure. |
42
Közepes
The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:
| A reduction in the amount of refrigerant and an increase in energy efficiency. |
| A reduction in the system’s energy efficiency. |
| An increase in the amount of refrigerant in the system and an increase in condensing pressure. |
| There is no effect whatsoever on either the amount of refrigerant or energy efficiency. |
43
Közepes
Which refrigerants belong to the HFC group?
| R134a, R32, R22, R507A, R290. |
| R134a, R404A, R507A, R410A. |
| R11, R12, R502. |
| R22, R401A. |
44
Közepes
Which refrigerants belong to the HFO group?
| R1234yf, R1234ze. |
| R134a, R290. |
| R134a, R404A. |
| R22, R12. |
45
Közepes
What are the characteristics of R410A refrigerant compared to R407C refrigerant?
| The saturation pressure of R407C is 150% higher than that of R410A. |
| The saturation pressure of both refrigerants is roughly the same. |
| The saturation pressure of R407C refrigerant is much higher than that of R410A. |
| The saturation pressure of R410A refrigerant is higher than that of R407C. |
46
Közepes
What does the TEWI parameter define?
| This is a parameter defining the ozone layer’s ability to recover (regenerate). |
| This is a parameter that quantifies the impact of refrigerants on the ozone layer. |
| It is the total (global) greenhouse gas equivalent – this indicator takes into account the refrigerant’s direct capacity to contribute to the greenhouse effect and its indirect impact on it through the energy consumption (during the production of which CO₂ is generated) by the refrigeration unit in operation. |
| It is the global warming potential, expressed in terms of carbon dioxide (CO₂), over a 100-year time horizon. |
47
Közepes
What are the characteristics of R452A refrigerant compared to R404A?
| It is a non-flammable refrigerant, a mixture from the HFC/HFO group with thermodynamic properties similar to those of R404A and a GWP approximately 45% lower than that of R404A. |
| The temperature glide of R452A is half that of R404A. |
| Both refrigerants are homogeneous refrigerants with no temperature glide. |
| It is a flammable and toxic homogeneous refrigerant from the HFC group. |
48
Közepes
What is the distinguishing feature of R1234yf compared to R134a?
| greater toxicity. |
| A higher critical temperature. |
| a higher boiling point at standard pressure. |
| greater flammability. |
49
Közepes
Compared to R134a, the refrigerant CO₂ is characterised by?
| It has identical thermodynamic properties and can be used as a drop-in replacement for R134a. |
| It has a lower critical temperature, higher operating pressures and greater volumetric efficiency, allowing for the use of a smaller quantity of refrigerant compared to R134a. |
| Unlike R134a, it is an azeotropic mixture. |
| It has a temperature slip of 7K greater than R134a. |
50
Közepes
The following are not classified as fluorinated greenhouse gases:
| Perfluorocarbons (PFCs). |
| Carbon dioxide (CO₂). |
| Sulphur hexafluoride (SF6). |
| Hydrofluorocarbons (HFCs). |
51
Nehéz
What additional protective equipment will you use when soldering systems containing HC refrigerants?
| Tinted safety goggles |
| Flammable gas detector |
| Fire blanket |
| High-visibility jacket |
52
Nehéz
Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?
| There is a risk of refrigerant leakage |
| The pressure switch setting will not be correct |
| Dust and moisture may enter |
| It is a potential source of ignition |
53
Nehéz
What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?
| 3 m |
| 1 m |
| 2 m |
| 0.5 m |
54
Nehéz
What is the maximum safe charge for a recovery cylinder with R32 refrigerant, if it can be charged with 20 kg of R410A?
| 9 kg |
| 20 kg |
| 18 kg |
| 33 kg |
55
Nehéz
According to EN 378, what is the maximum charge of an A3 refrigerant for a display unit (hermetic, with an internal condenser) located in the ground-floor retail area of a supermarket?
| 1.5 kg |
| 2.5 kg |
| 10 kg |
| 1.0 kg |
56
Nehéz
How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?
| There is no need to evacuate such systems |
| Position the vacuum pump 3 metres above floor level |
| Use an ATEX-certified vacuum pump in a well-ventilated area |
| Fit a long hose to the pump outlet to remove HC away from the system |
57
Közepes
What is the greenhouse effect?
| It causes the thermal radiation emitted by the Earth to be trapped in the upper atmosphere. |
| It alters the composition of the atmospheric air. |
| It causes an increase in temperature close to the Earth’s surface (up to 10 metres above the surface). |
| It lowers the average surface temperature of the Earth. |
58
Nehéz
What protective equipment must you have in your car when transporting flammable substances?
| Tinted safety goggles |
| A fire extinguisher |
| Thick gloves |
| Fire blanket |
59
Nehéz
How would you remove the refrigerant from a 10kg R32 water chiller, located outdoors, before unsoldering the connections?
| Recover the R32 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g |
| Vent the R32 to the outside; charge the system with nitrogen until an overpressure is achieved, vent and drain the system twice, charge the system with nitrogen a third time and vent |
| Vent the R32 to the outside and drain the system |
| Recover the R32 until a vacuum is achieved |
60
Közepes
What is R1270?
| Isobutane |
| Propene |
| Butane |
| Propene |
61
Nehéz
Which of the following leak detection methods cannot be used to locate an HC refrigerant leak?
| Soapy water solution |
| Electronic leak detector for flammable refrigerants |
| Electronic HFC leak detector |
| Leak detection foam |
62
Nehéz
What is the most important difference between a flammable refrigerant recovery unit and a standard one?
| A flammable refrigerant recovery unit has no ignition sources |
| Different low-pressure switch setting |
| Different connection sizes |
| A different colour for the station |
63
Nehéz
Which of the following is a source of ignition?
| ‘n’ type thermostat |
| Contactor |
| Ex-certified evaporator fan motor |
| Defrost heating element |
64
Nehéz
What substance is produced when R32 is burnt?
| Hydrochloric acid |
| Carbon monoxide |
| Hydrogen fluoride |
| Phosgene |
65
Nehéz
What type of refrigerant is R1234ze?
| Hydrochlorofluoro-hydrocarbon |
| Chloro-fluoro-hydrocarbon |
| Hydrocarbon |
| Hydrofluoroolefin |
66
Nehéz
What hazards does a Group A3 refrigerant pose?
| Low toxicity, highly flammable |
| High toxicity, moderate flammability |
| Low toxicity, moderate flammability |
| High toxicity, high flammability |
67
Nehéz
According to EN 378, what is the maximum charge of R290 in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R290 is 0.038 kg/m³)?
| 0.285 kg |
| 4.93 kg |
| 1.5 kg |
| 1.0 kg |
68
Könnyű
What does the GWP indicator mean?
| This is an indicator expressing the potential to deplete the ozone layer. |
| It is the global warming potential. The impact on global warming caused by 1 kg of a given gas or chemical substance, expressed as a GWP value, where GWP=1 represents the global warming caused by 1 kg of CO₂ over a period of 100 years (the global warming potential of a unit mass of a given gas over a 100-year period, relative to the warming caused by a unit mass of CO₂). |
| It is a unit expressing the ability to enhance the ozone layer. |
| It is an expansion of the abbreviation ‘Global Warming Potential’ and indicates the rate of increase in air temperature |
69
Nehéz
What is the cooling capacity of R32 compared to R410A?
| 60% |
| 130% |
| 75% |
| 105% |
70
Nehéz
Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?
| Because they must be kept running continuously to disperse the leaking refrigerant |
| To avoid a source of ignition in the event of a flammable refrigerant leak |
| Because they are more reliable |
| Because they are more energy-efficient |
71
Nehéz
Why is the difference in density between HC and HFC refrigerants important?
| Because it increases operating pressures |
| Because it affects energy efficiency |
| Because it affects the charge weight |
| Because it affects the charging rate |
72
Nehéz
What is the GWP value for R290?
| 675 |
| 7 |
| 3 |
| A. 0.02 |
73
Nehéz
Which of the following is not a source of ignition?
| An Ex-certified fan motor |
| Light switch |
| Open mechanical pressure switch |
| Electrical switch |
74
Nehéz
What is R290?
| Propylene |
| Butane |
| Propene |
| Propene |
75
Nehéz
According to EN 378, what is the maximum HC refrigerant charge for a display unit (hermetic system with an internal condenser) located in the ground-floor shopping area of a supermarket?
| 2.5 kg |
| 150 g |
| 1.5 kg |
| 1.0 kg |
76
Nehéz
Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?
| It could be a source of ignition |
| The method of starting the compressor motor differs from that used with HFCs |
| A relay is never required for compressors using flammable refrigerants |
| Current consumption differs for compressors using flammable refrigerants compared to those using HFCs |
77
Nehéz
What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?
| 1 m |
| 5 m |
| 10 m |
| 3 m |
78
Nehéz
What is the safe charge for a recovery cylinder with R290 refrigerant, if it can be charged with 10 kg of R404A?
| 17 kg |
| 8 kg |
| 3.6 kg |
| 20 kg |
79
Közepes
How do refrigeration systems contribute to the greenhouse effect, i.e. the rise in atmospheric temperature at the Earth’s surface?
| Refrigeration equipment emits CO₂ both directly and indirectly. |
| As a result of oil being emitted into the atmosphere by the condenser and filter |
| Through the leakage of refrigerant into the environment. |
| Indirectly (through energy consumption) and directly (through the emission of refrigerants into the atmosphere) |
80
Nehéz
How can a vacuum pump be used safely to evacuate a system containing R290?
| There is no need to evacuate systems containing R290 |
| Fit a long hose to the pump outlet to remove HC away from the system |
| Use an ATEX-certified vacuum pump in a well-ventilated area |
| Position the vacuum pump 3 metres above floor level |
81
Nehéz
In accordance with ADR regulations, what protective equipment must you have in your vehicle when transporting flammable refrigerants?
| Tinted safety goggles |
| Fire blanket |
| Thick gloves |
| A fire extinguisher |
82
Nehéz
How do you ensure it is safe to light the torch needed to desolder joints in a system that has been evacuated of flammable refrigerant?
| Purge the system with oxygen-free nitrogen |
| Ensure the area is well ventilated and use a flammable gas detector to check the area |
| You must not desolder joints on a system containing a flammable refrigerant; they must be cut using a pipe cutter |
| Work outdoors |
83
Nehéz
How would you remove the refrigerant from a system containing 100 g of R1270 so that it is ready for the joints to be desoldered?
| Vent the R1270 to the outside; charge the system with nitrogen until an overpressure is reached, vent and evacuate the system twice, charge the system with nitrogen a third time and vent |
| Recover the R1270 until a vacuum is achieved |
| Vent the R1270 to the outside and drain the system |
| Recover the R1270 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g |
84
Nehéz
Which of the following leak detection methods cannot be used to locate a leak of R290 refrigerant?
| Electronic HFC leak detector |
| Leak detection foam |
| Fluorescent dye and a UV lamp |
| Electronic leak detector for flammable refrigerants |
85
Nehéz
Why can’t recovery stations designed for HFCs be used with R600a?
| The oil in the recovery unit is not soluble in R600a |
| The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure |
| It contains ignition sources |
| The recovery unit cannot withstand the working pressure of R600a |
86
Nehéz
According to EN 378, what is the maximum charge of R1234ze in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R1234ze is 0.303 kg/m³)?
| 6.18 kg |
| 618 kg |
| 2.27 kg |
| 227 kg |
87
Nehéz
What type of refrigerant is R32?
| Carbon dioxide |
| Hydrofluoroolefin |
| Hydrofluorocarbon |
| Hydrocarbon |
88
Nehéz
What hazards do A2L refrigerants pose?
| High toxicity, high flammability |
| Low toxicity, high flammability |
| Low toxicity, moderate flammability |
| High toxicity, moderate flammability |
89
Nehéz
What danger is associated with the combustion of HFO or HFC refrigerants?
| Phosgene is produced |
| Citric acid is produced |
| Nitrous oxide is produced |
| Hydrogen fluoride is produced |
90
Közepes
What is the greenhouse effect, also known as the greenhouse phenomenon?
| It is the phenomenon of heat being trapped in the Earth’s atmosphere (making it difficult for heat to radiate out of the Earth’s atmosphere). |
| The filtering out of solar radiation. |
| This is the formation of a layer that traps only the heat generated by the combustion of fuel in aeroplanes. |
| The absorption of radiation reaching the Earth’s surface. |
91
Nehéz
What is the approximate displacement volume required for a compressor running on R600a compared to one running on R134a to achieve the same cooling capacity?
| Half |
| The same |
| Seven times |
| Twice |
92
Nehéz
What is the GWP value for R32?
| 0 |
| 7 |
| 3 |
| 675 |
93
Nehéz
Why is the accuracy of the charge weight more important for systems critically charged with R290 compared to those using HFCs
| Due to lower operating pressures |
| The charge mass is significantly lower than in an HFC system, as the density is much lower |
| Because R290 is only used in systems with a charge of less than 150g |
| Because these systems never have liquid receivers |
94
Nehéz
Why does the condenser fan run continuously in some systems using R1270?
| To ensure that the discharge pressure never becomes excessive |
| To reduce energy consumption |
| To dilute the refrigerant in the event of a leak |
| To prevent the build-up of contaminants in the condenser |
95
Közepes
Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?
| Regulation (EU) 2015/1188 |
| Regulation (EU) No 517/2014 |
| Directive 2009/125/EC |
| Regulation (EU) 2024/573 |
96
Közepes
What is the main objective of Regulation (EU) 2024/573?
| Prevention of F-gas emissions and the achievement of the EU’s climate targets |
| To facilitate the import of electrical appliances |
| Standardising metal recycling standards |
| To reduce taxes on refrigeration equipment |
97
Közepes
What are the obligations of manufacturers of refrigeration appliances in the context of ecodesign, and which regulation governs them?
| Manufacturers are only required to declare the quantity of F-gas used, in accordance with Regulation (EU) No 517/2014 |
| Manufacturers are only required to use energy labels, and this is regulated by Regulation (EU) 2024/573 |
| The manufacturer must ensure minimum energy efficiency, reparability and recyclability of equipment, as regulated by Regulation (EU) 2019/2019 |
| Manufacturers must comply solely with ISO 9001 standards, without any link to EU regulations |
98
Közepes
What is the main objective of the Ecodesign Directive?
| To standardise the appearance of products in the EU |
| To increase sales of electrical appliances in the EU |
| To facilitate the import of products from outside the EU |
| Reducing the negative environmental impact of products by improving energy efficiency, durability and recyclability |
99
Közepes
What is the function of a ball valve in a refrigeration system?
| It regulates the temperature of the refrigerant |
| It prevents excessive pressure build-up in the system |
| Enables the refrigerant flow to be completely shut off |
| It measures the moisture content of the refrigerant |
100
Könnyű
What is the main function of a relief valve?
| It controls the oil level in the compressor |
| Prevents the evaporator from freezing |
| Relieves pressure in the system in the event of excessive pressure |
| It monitors the moisture content of the refrigerant |
101
Közepes
How do certain substances or gases contribute to the greenhouse effect?
| When released into the atmosphere, certain substances cause the air to heat up as a result of reactions with the oxygen and nitrogen contained in the air. |
| Certain substances limit the impact of the Sun’s ultraviolet radiation on the Earth’s surface. |
| Some substances damage the ozone layer |
| Certain substances trap the thermal radiation that the Earth should radiate into the atmosphere. In this way, the Earth gradually warms up and the greenhouse effect occurs. |
102
Közepes
What is the purpose of the sight glass in a refrigeration system?
| To shut off the flow in the event of an emergency |
| To regulate compressor pressure |
| For visual assessment of the presence of refrigerant and oil, and for monitoring moisture levels |
| To measure the condenser temperature |
103
Közepes
What is the function of the temperature regulator in a refrigeration system?
| Controls the operation of the compressor and valves to maintain the set temperature |
| It drains excess refrigerant into the receiver |
| It restricts oil flow |
| To maintain a constant pressure in the compressor |
104
Nehéz
What is the role of the liquid separator in systems using flammable or toxic refrigerants?
| It prevents liquid from entering the compressor |
| Heats the refrigerant before it enters the evaporator |
| They are used solely to measure the moisture content of the refrigerant |
| It separates the liquid from the oil |
105
Nehéz
What is the function of an oil separator in systems using flammable or toxic refrigerants?
| Heats the refrigerant before it enters the evaporator |
| They are used solely to measure the moisture content of the refrigerant |
| It prevents liquid from entering the compressor |
| Separates oil from the refrigerant and facilitates the return of oil to the compressor |
106
Közepes
What is the purpose of oil level regulators in a refrigeration system?
| They drain off excess refrigerant |
| They control the pressure in the condenser |
| Maintains the correct oil level in the compressor |
| They control the evaporator temperature |
107
Közepes
What is the function of the refrigerant receiver in the system?
| It controls the evaporator temperature |
| Stores excess refrigerant and facilitates the detection of leaks |
| Regulates the oil flow |
| It maintains a constant pressure in the system |
108
Közepes
What is the role of the manifold thermometer in the refrigeration system?
| Relieves pressure in the system in the event of excessive pressure |
| Measures the refrigerant temperature at the compressor inlet and outlet, which helps to identify leaks |
| It monitors the moisture content of the refrigerant |
| Controls the oil level |
109
Közepes
What is the role of the defrost control valves?
| They drain off excess oil |
| They control the pressure in the compressor |
| They are used to monitor the moisture content of the refrigerant |
| Protect the evaporator from excessive icing and reduce the risk of leaks |
110
Nehéz
Why do CO₂ refrigeration systems require special attention when separating liquid and oil?
| CO₂ does not require lubrication, so separators are unnecessary |
| CO₂ operates at high pressure, which increases the risk of compressor failure and leaks |
| CO₂ is flammable, so separators cannot be used |
| CO₂ cannot be used in systems with sight glasses |
111
Nehéz
What is the critical pressure of CO₂ (R744)?
| Approximately 10 bar |
| Approximately 74 bar |
| Approximately 120 bar |
| Approximately 31 bar |
112
Könnyű
What is the base unit of pressure according to the International System of Units (SI)?
| Psi |
| Pa |
| bar |
| Atm. |
113
Közepes
Where can I find lists detailing fluorinated greenhouse gases (F-gases)?
| In the Regulation of the Minister for the Economy on the introduction of a list of fluorinated greenhouse gases. |
| In the Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases. |
| In Regulation (EU) No 2024/573 of the European Parliament and of the Council |
| In the Vienna Convention for the Protection of the Ozone Layer. |
114
Nehéz
What characterises the transcritical process in CO₂ systems?
| The system operates above the critical point and the refrigerant does not condense in the conventional manner |
| It occurs only at low temperatures |
| Conventional condensation occurs |
| It is irrelevant to the operation of the system |
115
Nehéz
What characterises the subcritical CO₂ process?
| Operation above the critical point |
| The absence of condensation |
| The conventional condensation process below the critical point |
| The absence of evaporation |
116
Nehéz
What is the log(p)-h diagram for CO₂ used for?
| To detect leaks |
| For analysing thermodynamic processes in a refrigeration system |
| To measure temperature |
| To regulate pressure |
117
Nehéz
What can be read from the log(p)-h graph?
| Pressure, enthalpy, temperature and state of the refrigerant |
| Only the temperature |
| Only the amount of refrigerant |
| Only the humidity |
118
Nehéz
What are CO₂ saturation tables used for?
| To regulate the compressor |
| To determine the oil quantity |
| To determine the relationship between temperature and pressure at saturation |
| To measure humidity |
119
Nehéz
What does the CO₂ saturation state mean?
| A state of high pressure |
| A state in which the refrigerant is only a gas |
| Equilibrium between the liquid and vapour phases |
| Dry ice state |
120
Nehéz
When can dry ice (solid CO₂) form?
| At high pressure |
| In the event of a sudden drop in pressure and temperature below the triple point |
| During normal operation of the system |
| At high temperature |
121
Nehéz
What risks are associated with the formation of dry ice in a CO₂ system?
| Improved efficiency |
| Blocked pipes and system damage |
| Pressure reduction |
| No risk |
122
Nehéz
How does the CO₂ pressure change as the temperature rises?
| It decreases |
| Rises sharply |
| It remains the same |
| It first decreases, then increases |
123
Nehéz
Why is understanding the log(p)-h graph particularly important for CO₂?
| It is only used for design purposes |
| It only applies to NH₃ |
| It doesn’t matter |
| As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis |
124
Közepes
Where can I find the lists specifying controlled substances?
| In Regulation (EU) No 2024/590 of the European Parliament and of the Council. |
| In the Vienna Convention for the Protection of the Ozone Layer. |
| In the current Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases. |
| In the Regulation of the Minister for the Environment on the list of controlled substances. |
125
Nehéz
What happens to CO₂ above the critical point?
| It turns into a solid |
| It transitions to a supercritical state (no distinction between liquid and gas) |
| It ceases to conduct heat |
| It turns into a liquid |
126
Nehéz
Why do CO₂ systems require precise pressure control?
| They do not require control |
| Due to low pressures |
| Because there are no valves |
| Due to significant pressure changes with temperature fluctuations |
127
Közepes
Why is ammonia (NH₃) considered a toxic refrigerant?
| It does not react with water, which makes it difficult to neutralise |
| It is highly irritating to the respiratory tract and toxic if inhaled |
| It is flammable and can form explosive mixtures with air |
| It is colourless and odourless, so it is difficult to detect |
128
Nehéz
What is the main difference between a dry evaporator and a flooded evaporator?
| A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas |
| A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator |
| A dry evaporator has a lower operating pressure than a flooded one |
| A dry evaporator does not require an expansion valve, whereas a flooded one does |
129
Nehéz
What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?
| Atmospheric pressure, approximately 1 bar |
| A pressure varying between 10 and 20 bar |
| Negative pressure (vacuum), below 0 bar |
| Positive pressure, in the range of 5–10 bar |
130
Nehéz
Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?
| They are climate-neutral |
| They are persistent, accumulate in the environment and may be toxic |
| They are readily biodegradable, so they only pollute the environment for a short time |
| They cause rapid cooling of the atmosphere |
131
Nehéz
What is the basic requirement when charging a system with R717 (NH₃)?
| Charging can be carried out without personal protective equipment |
| NH₃ can be charged together with air |
| Charging must only take place at temperatures below 0°C |
| Charging should take place in a well-ventilated area using appropriate personal protective equipment |
132
Nehéz
How should oil be handled in systems using R717?
| The oil does not require any monitoring |
| Oil can be mixed with any refrigerant |
| Oil has no effect on the system’s operation |
| The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks |
133
Nehéz
What is the correct procedure for recovering R717 from a system?
| Recovery is not required |
| The gas can be released into the atmosphere |
| The refrigerant can be drained into the sewer system |
| The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃ |
134
Nehéz
How should R717 (NH₃) be stored?
| Near heat sources |
| In any open containers |
| In unmarked plastic containers |
| In sealed, labelled containers, in a cool and well-ventilated place |
135
Közepes
Where and by when should annual reports on ODS and F-gases be submitted?
| Reports must be submitted by the end of the relevant calendar year, using a special form at the regional branch of the Office of Technical Inspection (UDT) |
| Reports for the previous year must be submitted by 31 March of the relevant year electronically to the Ministry of the Environment. |
| Reports for the previous year must be submitted by 31 January electronically by completing the special forms available in the central register of operators ‘CRO’. |
| Reports on ODS and F-gases for the previous year must be submitted by 28 February of the following year, via the IT system available in the reports database at the Office for the Protection of the Ozone Layer and Climate (BOWOiK) on the ICHP website. |
136
Nehéz
What should be done in the event of R717 contamination?
| The refrigerant must be purified or sent for disposal in accordance with regulations |
| Release into the atmosphere |
| Continue to use without restriction |
| Add water to dilute it |
137
Nehéz
What is the main hazard associated with an R717 leak during maintenance work?
| Toxic to humans and may cause chemical burns |
| No risk whatsoever |
| Damage to electrical equipment only |
| Increased cooling efficiency |
138
Nehéz
What action should be taken if an NH₃ leak is detected?
| Close your eyes and carry on working |
| Ignore it and carry on working |
| Increase the pressure in the system |
| Evacuate personnel immediately and remove the source of the leak, if it is safe to do so |
139
Nehéz
What role do scrubbers play in NH₃ systems?
| They increase the pressure in the system |
| They are used to measure temperature |
| They store the refrigerant |
| Neutralises ammonia through absorption in a liquid (e.g. water) |
140
Nehéz
How should the system be prepared before filling with R717?
| Check for leaks, remove air and moisture, and create a vacuum |
| Simply start it up |
| There is no need to check it |
| The pressure must be increased above the standard level |
141
Nehéz
What are the transport requirements for R717?
| It can be transported in open containers |
| Transport is not subject to regulations |
| Must be transported in suitable, labelled containers in accordance with ADR regulations |
| It can be transported without labelling |
142
Nehéz
What personal protective equipment is required when working with NH₃?
| No requirements |
| Workwear only |
| Only a safety helmet |
| Safety goggles, gloves and respiratory protective equipment |
143
Közepes
Which measure has the greatest impact on improving the compressor’s energy efficiency during installation?
| Correctly create a vacuum and remove moisture from the system |
| Increasing the amount of refrigerant |
| Installation without a leak test |
| Installation without filters |
144
Közepes
How does regular monitoring of the oil level affect the compressor’s operation?
| It has no effect |
| Causes a rise in pressure |
| Ensures proper lubrication and improves energy efficiency |
| It reduces cooling capacity |
145
Közepes
How do system leaks affect the compressor’s energy efficiency?
| These cause a drop in performance and an increase in energy consumption |
| Have no effect |
| They improve efficiency |
| They lower the operating temperature |
146
Közepes
Regulation (EC) No 2024/590 relates to:
| Health and safety at work during the recovery of refrigerants. |
| Alternative refrigerants serving as substitutes for fluorinated greenhouse gases. |
| The conditions for obtaining F-gas certificates by companies carrying out the recovery and reclamation of waste refrigerants. |
| Ozone-depleting substances. |
147
Közepes
What is the significance of regulating suction and discharge pressure?
| Helps maintain optimal operating conditions for the compressor |
| Causes leaks |
| Increases oil consumption |
| It has no effect on efficiency |
148
Közepes
What maintenance measure reduces the compressor’s energy consumption?
| Increasing the refrigerant charge |
| Lack of servicing |
| Regular replacement of filters and dryers |
| Disabling safety devices |
149
Közepes
How does the presence of air in the refrigeration system affect performance?
| Leads to increased pressure and reduced efficiency |
| Reduces energy consumption |
| It improves efficiency |
| It has no effect |
150
Közepes
What role do control systems (e.g. regulators) play in compressor efficiency?
| Causes leaks |
| It increases the amount of refrigerant |
| It doesn’t matter |
| Enables optimisation of operation and a reduction in energy consumption |
151
Közepes
How does refrigerant superheat at the compressor suction affect performance?
| It has no effect |
| It always improves performance |
| It only causes a drop in temperature |
| Excessive overheating reduces efficiency and increases energy consumption |
152
Közepes
How does the correct layout of the system affect efficiency?
| It doesn’t matter |
| It causes the temperature to rise |
| It increases the pressure |
| Shortens flow paths and reduces energy losses |
153
Közepes
How important is pipe insulation?
| It increases energy consumption |
| It has no effect |
| Reduces heat loss and improves energy efficiency |
| Causes a rise in pressure |
154
Közepes
Which measure most improves the condenser’s energy efficiency?
| Restricted airflow |
| Contamination of the heat exchange surface |
| Regular cleaning of heat exchange surfaces |
| Increasing the amount of refrigerant |
155
Közepes
How does a dirty condenser affect the operation of the refrigeration system?
| It improves efficiency |
| Causes an increase in pressure and energy consumption by the compressor |
| It has no effect |
| It lowers the condensing pressure |
156
Közepes
Why is adequate airflow through an air-cooled condenser important?
| Ensures effective heat dissipation and improves energy efficiency |
| Causes a drop in pressure |
| Insufficient airflow reduces efficiency |
| It doesn’t matter |
157
Közepes
Which refrigerants cause damage to the ozone layer?
| All refrigerants that contain carbon in their molecular structure. |
| All refrigerants that contain chlorine or bromine in their molecules. |
| All refrigerants that are hydrocarbon derivatives. |
| All refrigerants that contain fluorine and hydrogen in their molecules. |
158
Közepes
How does the presence of limescale in a water-cooled condenser affect performance?
| It improves heat transfer |
| It lowers the condensation temperature |
| Impairs heat exchange and increases energy consumption |
| It has no effect |
159
Közepes
How does correct condensation pressure control affect efficiency?
| It has no effect |
| It increases energy consumption |
| Causes leaks |
| Maintains optimum operating conditions and reduces energy consumption |
160
Közepes
How do condenser leaks affect energy efficiency?
| They lower the temperature |
| Have no effect |
| Causes refrigerant loss and a drop in efficiency |
| They improve efficiency |
161
Közepes
How important is the correct positioning of an air-cooled condenser?
| It doesn’t matter |
| It should be close to heat sources |
| It should be housed in a small room |
| It should be installed in a well-ventilated area with unobstructed airflow |
162
Közepes
How does hot air recirculation affect the condenser?
| It reduces the pressure |
| It improves efficiency |
| Impairs cooling and increases energy consumption |
| It has no effect |
163
Közepes
How does the insulation of central heating and domestic hot water pipework affect the operation of the heat pump’s condenser?
| It increases the pressure |
| It doesn’t matter |
| Reduces energy losses and improves the efficiency of the entire system |
| It impairs cooling |
164
Közepes
Which measure most improves the energy efficiency of the evaporator?
| Restricted airflow |
| Increasing the amount of refrigerant |
| Increasing the condensation temperature |
| Regular defrosting of the evaporator |
165
Közepes
How does evaporator icing affect the system’s operation?
| It has no effect |
| Impairs heat exchange and increases energy consumption |
| It improves cooling performance |
| It lowers the condensation temperature |
166
Közepes
How does dirt on the evaporator surface affect its performance?
| It reduces the pressure |
| It improves efficiency |
| Impairs heat exchange and increases energy consumption |
| It has no effect |
167
Közepes
What maintenance task is crucial for the evaporator?
| Increasing the refrigerant charge |
| Reduced airflow |
| Regular cleaning and defrosting |
| Lack of maintenance |
168
Közepes
What does an F-gas personal certificate (Category A2) authorise?
| To recover refrigerant from equipment containing less than 3 kg of fluorinated greenhouse gases, or less than 6 kg in the case of hermetically sealed systems. |
| to make permanent joints by brazing in systems containing fluorinated greenhouse gases. |
| for the purchase of lubricants and refrigeration oils, and for the testing of safety valves. |
| to repair, maintain or service refrigeration equipment and systems containing controlled substances. |
169
Közepes
How does superheating of the refrigerant at the evaporator outlet affect efficiency?
| It has no effect |
| It always improves performance |
| It only causes a drop in temperature |
| Excessive superheat reduces energy efficiency |
170
Közepes
How do leaks in the evaporator affect efficiency?
| These cause refrigerant loss and a drop in efficiency |
| Increase capacity |
| Have no effect |
| Improves performance |
171
Közepes
How important is correct expansion valve adjustment?
| It doesn’t matter |
| Ensures optimal evaporator charge and improves efficiency |
| It increases energy consumption |
| Causes leaks |
172
Közepes
How does inadequate insulation of the heat transfer circuit pipes affect evaporator performance?
| It improves efficiency |
| Causes cooling losses and increased energy consumption |
| It has no effect |
| It lowers the condensation temperature |
173
Közepes
How does correct TEV valve adjustment affect the system’s energy efficiency?
| Ensures optimum superheat and improves system efficiency |
| Causes leaks |
| It increases energy consumption |
| It has no effect |
174
Közepes
What happens if the superheat set by the TEV is too high?
| The refrigerant charge will increase |
| It has no effect |
| Cooling efficiency will improve |
| Efficiency will drop because the evaporator is not being fully utilised |
175
Közepes
How does a low superheat setting on the TEV affect performance?
| It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid |
| It reduces refrigerant flow |
| It has no effect |
| It increases operational safety |
176
Közepes
How do contaminants in the system affect the operation of the TEV?
| They improve its performance |
| Have no effect |
| They can cause it to become blocked and reduce efficiency |
| They lower the temperature |
177
Közepes
What role does the filter-drier play in terms of system efficiency?
| It doesn’t matter |
| It lowers the temperature |
| Removes moisture and contaminants, improving the system’s efficiency |
| It increases the amount of refrigerant |
178
Közepes
How does proper insulation of components (e.g. pipes near the TEV) affect the system?
| It doesn’t matter |
| It increases energy consumption |
| Prevents unwanted heat gains and improves efficiency |
| It causes leaks |
179
Közepes
What does Regulation (EU) No 2024/573 of the European Parliament and of the Council cover?
| The Regulation sets out requirements relating to brazing of refrigeration systems. |
| The Regulation sets out health and safety requirements for soldering work. |
| The Regulation concerns gases that contribute to the greenhouse effect. |
| The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements relating to leak testing of such equipment. |
180
Közepes
How important is it to check the operation of the condensing pressure control valve in the system?
| Ensures operation within the optimum pressure range and reduces energy losses |
| It has no effect |
| It increases energy consumption |
| It causes a significant rise in temperature |
181
Közepes
How does the correct selection of a TEV affect energy efficiency?
| Ensures the system is matched to its capacity and operates optimally |
| It doesn’t matter |
| It increases the amount of refrigerant |
| It lowers the temperature |
182
Közepes
What is the main design difference in hydrocarbon-based refrigeration systems?
| No need for safety measures |
| Lower energy efficiency |
| Higher operating pressures |
| The need for explosion-proof measures due to the flammability of the refrigerant |
183
Közepes
What differences are there in the compressors used in hydrocarbon systems?
| They must be designed to operate with flammable refrigerants (e.g. hermetic compressors) |
| No differences |
| They must operate at higher pressures |
| They do not require lubrication |
184
Nehéz
What is the main characteristic of R744 (CO₂) refrigeration systems?
| Very high operating pressures |
| No need for regulation |
| Low energy efficiency |
| Low operating pressures |
185
Nehéz
What are the requirements for piping materials in CO₂ systems?
| They may be made of any material |
| They must be made exclusively from plastics |
| It does not matter |
| They must be able to withstand high pressures (e.g. high-grade steel) |
186
Nehéz
How does a booster system work in CO₂ installations?
| It is used to store the refrigerant |
| It reduces the amount of refrigerant |
| It utilises two stages of compression (low and medium pressure) in a single system |
| It reduces the pressure in the evaporator |
187
Nehéz
What is the function of high-pressure control valves in CO₂ systems?
| They lower the evaporator temperature |
| They are used to store the refrigerant |
| They control the pressure on the high-pressure side and optimise system operation |
| They regulate oil flow |
188
Nehéz
Why is pressure optimisation in CO₂ systems crucial?
| It reduces the ambient temperature |
| It reduces the amount of refrigerant |
| It enables the system to achieve maximum energy efficiency |
| It doesn’t matter |
189
Nehéz
What role do parallel-operating compressors play in CO₂ systems?
| They lower the ambient temperature |
| It does not matter |
| They increase energy consumption |
| They enable gas recovery from the medium-pressure stage and improve efficiency |
190
Közepes
How can one check whether the system has been overcharged with refrigerant?
| The refrigeration system is overcharged with refrigerant whilst in operation, and even under a very small heat load, frost forms on the suction side of the compressor |
| The compressor will operate under a lower load and the suction pressure will decrease |
| Under normal conditions, there is a marked increase in condensing pressure because an excessive amount of refrigerant accumulates in the condenser, reducing the heat exchange surface area within it. |
| This cannot be checked with sufficient reliability, as the sight glass is not designed for this purpose. |
191
Nehéz
How does an ejector work in a CO₂ system?
| It increases the amount of refrigerant |
| It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency |
| Stores the refrigerant |
| It lowers the evaporator temperature |
192
Nehéz
What is the function of liquid ejectors in CO₂ systems?
| They assist with liquid recovery and improve evaporator feed |
| They increase the amount of oil |
| They reduce atmospheric pressure |
| They raise the refrigerant temperature |
193
Nehéz
What are the characteristics of partially flooded systems in CO₂ systems?
| The absence of liquid in the evaporator |
| Low operating pressure |
| Lack of regulation |
| The presence of liquid in the evaporator, which improves heat transfer and efficiency |
194
Nehéz
What is the main risk associated with static pressure in CO₂ systems?
| A rise in pressure resulting from the refrigerant heating up whilst at rest |
| A decrease in refrigerant quantity |
| Increased efficiency |
| A drop in temperature |
195
Nehéz
How can standstill pressure in CO₂ systems be reduced?
| By increasing the temperature |
| By shutting down the system completely |
| By using parallel compressors and external cooling systems |
| By increasing the refrigerant charge |
196
Nehéz
What does ‘stagnation’ of a refrigeration system mean in the context of CO₂?
| Normal system operation |
| Improved efficiency |
| A drop in temperature |
| A lack of refrigerant flow, which can lead to increased pressure and safety risks |
197
Nehéz
Why do CO₂ systems require more advanced automation than traditional systems?
| Due to low pressures |
| Due to the need for precise control of pressure and temperature |
| Because there are no valves |
| They do not require automation |
198
Nehéz
What must be included on the label of a cylinder containing a flammable refrigerant?
| Net weight only |
| The name of the refrigerant, the hazard symbol and basic safety information |
| Information about the cylinder owner |
| Agent name only |
199
Nehéz
Why does the absence of a ‘flammable agent’ label on the system pose a significant hazard?
| It has no significant impact on safety |
| It reduces the system’s efficiency |
| It may lead to the incorrect selection of oil |
| It may lead to the use of tools that are a source of ignition |
200
Nehéz
Which set of information on the label of a flammable agent cylinder is crucial from a safety perspective?
| Gross weight and batch number |
| Manufacturer’s name and country of origin |
| Name of the substance, hazard pictogram, UN number |
| Cylinder colour and date of manufacture |
201
Közepes
Before charging the refrigeration unit with refrigerant, it is essential to…
| carry out a leak test. |
| check the compressor’s suction and discharge connections. |
| complete the unit’s data sheet. |
| carry out a start-up test. |
202
Nehéz
What is the requirement regarding the labelling of an installation containing a flammable substance?
| Labelling is required only in technical rooms |
| The labelling must indicate the type of substance and the flammability hazard |
| Labelling is not required for hermetically sealed systems |
| Colour-coding of pipes is sufficient |
203
Nehéz
What are the potential consequences of using unsuitable connections in a system containing a flammable substance?
| Merely a reduction in efficiency |
| Risk of leakage and the formation of an explosive mixture |
| No impact on safety |
| Merely installation difficulties |
204
Nehéz
What is the purpose of installing gas detectors in a room with a refrigeration system?
| Regulating compressor capacity |
| Early detection of refrigerant leaks and prevention of health risks |
| Measuring the refrigerant temperature |
| Monitoring pipe pressure |
205
Nehéz
How often should gas detection sensors in the service room be checked?
| Before each start-up of the unit |
| In accordance with the manufacturer’s instructions and applicable health and safety regulations |
| Only after a leak has occurred |
| Once every 5 years |
206
Nehéz
Where should a gas detector be positioned in accordance with EN 378?
| Anywhere in the room |
| On the ceiling if the gas is lighter or heavier than air; near the floor if it is lighter or heavier |
| Only at the entrance to the room |
| Near the control panel |
207
Nehéz
How should an employee respond when a gas alarm is triggered?
| Reduce the pressure in the system |
| Leave the room immediately and notify their supervisor |
| Switch off the system and wait for the alarm to stop |
| Carry on working until they see a leak |
208
Nehéz
What safety checks should be carried out when installing a new refrigeration system?
| The colour of pipes and hoses |
| Only the compressor power |
| The presence of health and safety signage, adequate ventilation and gas detectors |
| Is the air filter new? |
209
Nehéz
Gas detectors should be installed in rooms where:
| The amount of refrigerant exceeds a specified permissible threshold |
| The room is less than 5 m² |
| Ventilation is natural |
| Any refrigerant is present, regardless of the quantity |
210
Nehéz
What is the minimum number of emergency exits in a plant room (refrigeration plant room) and how should they be signposted?
| One exit, clearly marked in the direction of escape |
| One exit with an information sign about the refrigerant |
| Exits do not need to be signposted if the room is small |
| At least two exits, but signage is optional |
211
Nehéz
Which measure, when installing a system using a flammable refrigerant, improves its energy efficiency?
| No leak test |
| Restriction of ventilation |
| Thorough leak testing and vacuuming |
| Increasing the refrigerant charge |
212
Közepes
What information must appear on the unit’s label?
| Markings regarding the weight and capacity of the pipework, together with the colour code and chemical composition of the paints used to coat the frame and casing. |
| The manufacturer’s logo and the weight of the unit. |
| Among other things: information stating that the unit contains a fluorinated greenhouse gas, together with the industrial designation of the gas or its chemical name, the mass of the gas and its CO₂ equivalent |
| It does not matter what should be included on the device label. |
213
Nehéz
How do leaks affect systems using flammable refrigerants?
| They lower the temperature |
| They improve efficiency |
| Have no effect |
| They cause refrigerant loss, reduced efficiency and a fire hazard |
214
Nehéz
Why is it important to limit the amount of refrigerant in HC systems?
| It increases efficiency |
| It has no effect |
| It lowers the temperature |
| It reduces the risk of explosion and improves the system’s operational safety |
215
Nehéz
Why is the cleanliness of heat exchangers in HC systems important?
| It increases the pressure |
| It doesn’t matter |
| It improves heat transfer and reduces energy consumption |
| Causes leaks |
216
Nehéz
What maintenance measures improve the efficiency of a system using a flammable refrigerant?
| Regular checks for leaks and operating parameters |
| Increasing the refrigerant charge |
| Lack of servicing |
| Disabling safety devices |
217
Nehéz
How does the correct selection of components affect a system using a flammable refrigerant?
| It doesn’t matter |
| It lowers the temperature |
| It increases the amount of refrigerant |
| It ensures safe and optimal operation and minimises energy losses |
218
Nehéz
Why is it important to use the correct service tools in HC systems?
| It ensures operational safety and reduces refrigerant losses |
| It increases energy consumption |
| It doesn’t matter |
| Causes leaks |
219
Nehéz
How does pipe insulation affect the efficiency of systems containing HC?
| It doesn’t matter |
| It increases the pressure |
| It reduces energy losses and improves efficiency |
| Causes leaks |
220
Nehéz
Which safety class applies to R744?
| A2 |
| A1 |
| A3 |
| B2L |
221
Nehéz
In an R744 system operating in supercritical mode, the refrigerant entering the evaporator expansion valve is...
| A subcooled liquid |
| Saturated vapour at intermediate pressure |
| A supercritical fluid |
| A two-phase mixture at intermediate pressure |
222
Nehéz
In R744 supercritical systems, the gas cooler outlet valve controls:
| The outlet temperature of the gas cooler |
| The inlet temperature to the gas cooler |
| The gas cooler fans |
| The pressure in the gas cooler |
223
Közepes
What is the base unit of temperature according to the International System of Units (Système International d’Unités)?
| °F |
| °R |
| °C |
| K |
224
Közepes
Which of the following are the most important pieces of information that should be included in the unit’s data sheet:
| Information regarding refrigerant recovery and unit dismantling. |
| The make and model of the unit, so that the manufacturer can be contacted to obtain the technical information necessary for servicing. |
| Operator details, unit details, type and quantity of refrigerant, information regarding servicing and repairs. |
| The owner, installer and service technician of the unit. |
225
Nehéz
Which statement best describes the behaviour of R717 and mineral compressor oil?
| R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717 |
| R717 mixes very well with compressor oil and easily returns to the compressor |
| R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717 |
| In an R717 system, a return oil line cannot be used because the oil is too hot |
226
Nehéz
What is the main reason for using K65 copper tubing in some R744 systems?
| They can withstand higher pressures |
| They bend easily |
| They come in a wider range of diameters |
| They have good low-temperature performance |
227
Nehéz
Which of the following statements is correct regarding the installation of Schrader valves?
| Schrader valves must not be used in R744 systems |
| Hydrocarbons leak through Schrader valves |
| When brazing the valve body to the system, the core must be removed, then refitted and tightened to the correct torque |
| All Schrader valve cores are suitable for all refrigerants |
228
Nehéz
Which refrigerant can be detected using phenolphthalein paper?
| R744 |
| R1270 |
| R717 |
| R1234ze |
229
Nehéz
How does a refrigerant shortage affect the high-pressure side of the system (without discharge pressure regulation)?
| Discharge pressure will be lower, subcooling will be higher |
| Discharge pressure will be higher, and the degree of subcooling will be higher |
| Discharge pressure will be higher, and the degree of subcooling will be lower |
| The discharge pressure will be lower, and the subcooling will be lower |
230
Nehéz
What is the benefit of using helium as a tracer gas in nitrogen during a pressure test?
| It has a higher pressure than pure nitrogen |
| It is non-flammable |
| It has a distinct odour |
| It has smaller molecules and diffuses more easily |
231
Nehéz
Why should an R744 system that has been drained be initially charged with the refrigerant in gaseous form?
| To prevent damage to the compressor |
| To prevent the drain valve from opening |
| To ensure that R744 is charged slowly |
| To prevent the formation of dry ice |
232
Nehéz
If an R744 system contains moisture because it has not been properly drained, what is the likely consequence?
| Reduced cooling capacity |
| The formation of carbonic acid, which will cause damage to the system |
| Excessively high discharge pressure |
| The formation of hydrogen fluoride, which will decompose into hydrofluoric acid and damage the compressor |
233
Nehéz
Which system may require manual oil recovery?
| Secondary system using R744 |
| Supercritical ‘booster’ system using R744 |
| An R717 system |
| R744 cascade system |
234
Nehéz
The pressure of R744 at a saturation temperature of 20 °C is approx.
| 90 bar g |
| 56 bar g |
| 25 bar g |
| 14 bar g |
235
Közepes
Who is responsible for drawing up the equipment or installation record?
| There is no such obligation. |
| The person responsible for risk assessment. |
| The operator of the unit or system. |
| The equipment maintenance technician. |
236
Nehéz
Which refrigerant is lighter than air?
| R717 |
| R1234ze |
| R744 |
| R1270 |
237
Nehéz
What hazards are associated with a Class A3 safety agent?
| High flammability, lower toxicity |
| Lower toxicity, does not propagate flames |
| Slightly flammable, lower toxicity |
| High toxicity, does not propagate flames |
238
Nehéz
18 What is the GWP of R32 (according to AR4)?
| 6 |
| 0 |
| 3945 |
| 675 |
239
Nehéz
What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?
| Practical limit, room volume |
| Lower flammability limit, room volume |
| Lower flammability limit, height of the indoor unit, floor area |
| Practical limit, height of the indoor unit, floor area |
240
Nehéz
What compressor displacement is required for R1270, relative to R404A compressors for the medium-temperature range (cold store)?
| 150% |
| 600% |
| 50% |
| Similar |
241
Nehéz
At an ambient temperature of 25°C, the standby pressure in the low-pressure stage of an R744 cascade system will typically be…
| 27.5 bar g |
| The same as the high-pressure setting on the pressure switch |
| The same as the pressure set on the relief valve |
| Higher than the maximum permissible pressure in the low-pressure stage |
242
Nehéz
What is the correct definition of critical temperature?
| The temperature above which there are no distinct liquid and gaseous phases |
| The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid |
| The temperature at which a substance changes from a gaseous to a solid state |
| The temperature at which, for certain substances, electrical resistance is zero |
243
Nehéz
In a supercritical system, under supercritical conditions, the working fluid in the gas cooler
| it loses heat when its pressure drops |
| loses heat during a phase change |
| loses heat at constant temperature and pressure |
| it loses heat as its temperature drops |
244
Nehéz
R717 is highly corrosive to
| titanium |
| copper |
| stainless steel |
| aluminium |
245
Nehéz
What is the effect of repeatedly opening the relief valve?
| The valve remains fully open continuously |
| The valve will not open |
| The relief pressure drops |
| The relief pressure rises |
246
Közepes
Oil traps on the suction pipework are required:
| before the compressor. |
| at the inlet to each component of the refrigeration system. |
| always before any rise in the pipeline. |
| before the safety valve. |
247
Nehéz
What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?
| P2 = T1/(P1 × T2) |
| P2 = (P1 × T1)/T2 |
| P2 = (P1 × T2)/T1 |
| P2 = T2/(P1 × T1) |
248
Nehéz
What is the recommended alarm level for fixed leak detection systems for R717?
| 500,000 ppm |
| 500 ppm |
| 5,000 ppm |
| 50,000 ppm |
249
Nehéz
Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?
| Because compressors with a separate motor are cheaper |
| To increase the amount of refrigerant in the system |
| To reduce the condensing pressure |
| Because NH₃ reacts with the motor windings and hermetic compressors are not used |
250
Nehéz
Which type of compressor is most commonly used in large ammonia systems?
| A reciprocating or screw compressor |
| Rotary vane compressor |
| Diaphragm compressor |
| Hermetic scroll |
251
Nehéz
How is the capacity of a piston compressor regulated in NH₃ systems?
| By increasing the condensing pressure |
| By unloading the cylinders or changing the rotational speed |
| By reducing the refrigerant charge |
| Solely by adjusting the oil volume |
252
Nehéz
How is the capacity of a screw compressor most commonly controlled?
| By using a slide valve |
| By adjusting the oil level |
| By changing the type of oil |
| By closing the suction valve |
253
Nehéz
When is two-stage compression used in NH₃ systems?
| Exclusively in small systems |
| At small temperature differences |
| Only with water-cooled condensers |
| At very low vapour pressures and high pressure differentials |
254
Nehéz
What is the advantage of two-stage compression over single-stage compression?
| Lower efficiency |
| Higher energy consumption |
| Higher efficiency and lower discharge temperature |
| No need for a separator |
255
Nehéz
How does an evaporative condenser used in NH₃ systems work?
| Operates without a fan |
| It utilises the evaporation of water to increase cooling efficiency |
| It does not require a water supply |
| It transfers heat only to the air |
256
Nehéz
What is the function of the liquid separator in an NH₃ system?
| Increases the discharge temperature |
| Regulates the condensing pressure |
| It separates oil from the refrigerant |
| It prevents liquid from entering the compressor |
257
Közepes
When is there a refrigerant leak, even though the compressor is still running?
| When the condensing pressure and suction pressure rise, but there is no superheat. |
| When we observe a rise in the refrigerant level in the liquid receiver and the subcooling increases. |
| When the suction pressure is low, superheat is high, subcooling is negligible and the temperature difference between the condenser and the expansion valve is small. |
| When the sight glass is full of liquid refrigerant and we observe a rise in the oil level in the compressor sump. |
258
Nehéz
What is the purpose of monitoring the liquid level in the separator?
| To reduce the condensing temperature |
| To increase the oil volume |
| To control the condenser fan |
| To maintain the correct refrigerant level and prevent the compressor from flooding |
259
Nehéz
What is the role of the float switch in NH₃ systems?
| It monitors the liquid level in the tank or separator |
| It regulates the condensation temperature |
| It is used to detect leaks |
| It controls the fan’s operation |
260
Nehéz
What is a thermosiphon in NH₃ systems?
| An oil circulation system utilising differences in pressure and temperature |
| A type of safety valve |
| A defrosting device |
| A type of evaporator |
261
Nehéz
Why are oils that are immiscible with the refrigerant used in NH₃ systems?
| Because the oil mixes only with water |
| Because NH₃ does not mix with most compressor oils |
| To reduce the pressure |
| To increase the amount of refrigerant |
262
Nehéz
What is the main function of an oil separator in NH₃ systems?
| To separate the oil from the refrigerant and return the oil to the compressor |
| To lower the condensation temperature |
| To increase fan efficiency |
| Removing moisture from the system |
263
Nehéz
Which NH₃ system features direct evaporation of the refrigerant in the evaporator?
| Direct expansion (DX) system |
| Indirect system |
| Thermosiphon system |
| Glycol system |
264
Nehéz
What is the characteristic feature of a flooded evaporator system?
| No level control is required |
| No separator is used |
| The evaporator contains a large amount of liquid, which improves heat transfer |
| The evaporator is filled exclusively with vapour |
265
Nehéz
What is the main difference between a direct and an indirect system?
| In an indirect system, NH₃ flows directly into the space being cooled |
| In a direct system, there is no evaporator |
| In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load |
| In an indirect system, no compressor is used |
266
Közepes
Which components of a refrigeration system can be classified as potential leak points (leaks) subject to regular leak tests?
| Hermetic compressors, liquid refrigerant tanks and liquid separators. |
| All parts of the refrigeration unit that are connected to the suction side of the refrigeration system. |
| Fittings, valves including their stems, seals – including those in replaceable filters and dryers, components exposed to vibration, and connections to measuring, control and safety devices. |
| Parts of the system located on the high-pressure side (from the compressor up to and including the expansion valve). |
267
Közepes
What is the test pressure during the pressure leak test of the unit?
| The test pressure (maximum) is 30 bar. |
| The test pressure for leak testing is equivalent to the maximum operating pressure measured during the operation of the refrigeration unit. |
| The test pressure is determined by the person carrying out the leak test based on their experience. |
| According to the PN-EN 378 standard, at least 0.25 times the maximum permissible pressure for the system (PS). |
268
Közepes
In which part of the refrigeration unit must the recommended leak test be carried out?
| The test must be carried out on the compressor shut-off valves, solenoid valves and filters. |
| The check should only be carried out at the connection points for measuring instruments (pressure switches, pressure gauges, temperature sensors). |
| The test must be carried out at all points on the refrigeration unit where there is a potential risk of refrigerant leakage. |
| The check must be carried out on all parts of the refrigeration system that are connected to the discharge side of the refrigeration circuit. |
269
Közepes
When can a given unit be considered perfectly leak-tight?
| A device can be considered perfectly leak-tight if gas bubbles appear when it is submerged in water. |
| A given device can be considered perfectly leak-tight when the pressure drop during the test does not exceed 0.1 bar. |
| The device in question is perfectly leak-tight when we have carried out a check using a permanently installed electronic detector. |
| A given unit can be considered perfectly leak-tight if, during a leak test, the pressure remains constant, taking into account pressure changes caused by temperature variations. Any drop in pressure indicates a leak and requires the location of the leak to be identified. |
270
Közepes
What does EU Regulation 1516/2007 cover?
| The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements for leak testing of such equipment. |
| The Regulation addresses the disposal of gases that contribute to the greenhouse effect. |
| The Regulation sets out health and safety requirements for soldering work. |
| The Regulation sets out requirements relating to brazing of refrigeration systems. |
271
Nehéz
Which parts of refrigeration systems must be inspected on a mandatory and regular basis in accordance with EU Regulation 1516/2007?
| Connections on the condenser, as there is high pressure and the refrigerant is in liquid form |
| Fittings, 2. valves, 3. seals, 4. parts/components exposed to vibration, 5. connections at safety devices. |
| Only compressor connections, as these are subject to vibration. |
| Compressor connections, 2. connections on the liquid refrigerant tank |
272
Könnyű
What is superheat?
| It is the amount of heat required to turn a liquid into vapour. |
| It is the amount of heat required to increase the pressure. |
| It is the amount of heat required to cause the vapour formed from a liquid to become superheated. |
| It is the amount of heat required to heat a liquid. |
273
Nehéz
In accordance with EU Regulation 1516/2007, there are several methods of leak testing. What are these methods called?
| We distinguish between methods for quality control of supplied materials and leak testing methods that do not involve quality control of supplied materials. |
| We distinguish between direct and indirect methods of leak detection. |
| We distinguish between quality control methods for supplied materials and electronic testing methods. |
| We distinguish between physical and chemical methods. |
274
Nehéz
In accordance with EU Regulation 1516/2007, to whom can we entrust the responsibilities for leak testing of refrigeration systems?
| The check may be carried out by a specialist in leak testing. |
| The test may only be carried out by a competent person with the relevant skills, who holds a certificate attesting to the necessary knowledge in this field. They must also hold a certificate for companies regarding the operation and maintenance of refrigeration equipment charged with F-gases. |
| The check may only be carried out by a person who has previously carried out such a check. |
| The inspection may be carried out by a person employed and appointed by the owner of the installation. |
275
Nehéz
In accordance with EU Regulation 1516/2007, what conditions must be met in order to carry out a leak test on refrigeration systems using ultraviolet (UV) light?
| The manufacturer of the refrigeration equipment must confirm that the aforementioned UV method can be used. A UV leak test may be carried out by a qualified person who holds the relevant qualifications (certificate). |
| A prerequisite for carrying out a leak test using UV is having the appropriate technical resources, the relevant materials supplied, and suitable safety goggles. |
| A prerequisite for carrying out the inspection is holding the relevant authorisation for pressure testing issued by the UDT. |
| A prerequisite for carrying out a leak test using UV is that such a test is technically feasible. |
276
Nehéz
In accordance with EU Regulation 1516/2007, which leak testing methods are classified as direct leak testing methods?
| Leak test following the creation of a vacuum and leak detection using a foaming solution. |
| Leak test using nitrogen with a tracer gas, an electronic detector and pressure measurement. |
| Detection of leaks using a handheld leak detector and/or a fixed leak detection system; 2. Detection of leaks using a special dye with UV-fluorescent properties; 3. Detection of leaks using a foaming solution. |
| Leak testing by measuring pressure changes and the method of submerging the device/system in water. |
277
Nehéz
In accordance with EU Regulation 1516/2007, which methods are classified as indirect leak testing methods?
| This method is based on the analysis of the following parameters: pressure, temperature, operating pressure, liquid level, oil leakage, etc. |
| This method is based on electronic leak detection. |
| Leak detection using a UV tracer. |
| It utilises pressure and temperature measurements, as well as an ultrasonic method. |
278
Közepes
How should the pressure be increased during a pressure leak test?
| We increase the pressure gradually whilst checking for leaks, until the test pressure is reached, at a rate of no more than 2 bar/min |
| We increase the pressure at a rate of 10 bar/s. |
| We increase the pressure as quickly as possible. |
| We increase the pressure in any way. |
279
Közepes
What electronic equipment should be used to carry out leak testing?
| Only with devices fitted with an infrared detector. |
| Only with devices fitted with an ‘Ion Pump’ sensor. |
| Only with devices fitted with hot cathodes. |
| Only using devices with verified measurement sensitivity. |
280
Közepes
What documentation should be checked before starting a leak test?
| The maintenance log and the machine/device operating instructions must be checked. |
| Check the stock ledger (accounts). |
| Check the operating instructions for the machine/equipment. |
| Check the time sheets of the staff responsible for the machinery/equipment. |
281
Közepes
What information must be recorded when drawing up the leak test report?
| The number of locations where leaks have occurred and the date of the inspection. |
| The method used to carry out the leak test, the number of faults, the method of repairing the faults, the time taken to work on the installation, and the cost of the repair. |
| The date of the inspection, the number of faults (leaks), the location of the faults (leaks), the proposed method of rectifying the fault/defect (leak), attached documents and a signature. |
| The date of the inspection, a record of the occurrence of the leak, and a signature. |
282
Közepes
What pressure values should be used for the pressure leak test?
| The pressure for the leak test is 2–3 bar. |
| At the discretion of the person authorised to carry out the pressure test. |
| Use a pressure not exceeding the maximum permissible pressure for the system (PS). |
| The pressure value for the leak test is 10–12 bar. |
283
Közepes
What is temperature slip?
| It involves a decrease in temperature. |
| A specific temperature corresponds to a given vapour pressure. |
| A specific temperature cannot be assigned to a given vapour pressure. There is a temperature difference between the start and end of evaporation. |
| It involves an increase in temperature. |
284
Nehéz
What does a vacuum leak test involve?
| With the vacuum pump switched on, check whether the pressure in the system rises as a result of a leak. |
| After switching off the vacuum pump, we check whether the pressure in the system rises |
| If the pressure in the refrigeration system were to rise, we switch on the vacuum pump as required. |
| With the vacuum pump running continuously, we are able to maintain the required vacuum level in the system. |
285
Nehéz
How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?
| At least once every 12 months. |
| Only when servicing the unit. |
| On initial commissioning. |
| Once every six months. |
286
Nehéz
How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?
| Once every six months. |
| At least once every 12 months. |
| On initial commissioning. |
| Only when servicing the unit. |
287
Közepes
In which appliances and systems is the installation of a permanent leak detection system required?
| In equipment and installations containing at least 30 kg of fluorinated greenhouse gases. |
| In equipment and systems containing at least 5 tonnes of CO₂ equivalent. |
| In equipment and systems containing at least 500 tonnes of CO₂ equivalent. |
| In equipment and systems containing at least 50 tonnes of CO₂ equivalent. |
288
Nehéz
In accordance with Regulation (EU) 2024/573 of the European Parliament and of the Council, a fixed leak detection system is required when:
| The refrigeration equipment is operated in an enclosed space. |
| The refrigerant charge of the refrigeration equipment is at least 100 kg of ODS. |
| The installation of a fixed leak detection system is optional, but it helps to reduce the number of leak checks required on the equipment each year. |
| The charge of an F-gas refrigerant in a refrigeration unit is at least 500 tonnes of CO₂ equivalent. |
289
Nehéz
Under Regulation (EC) No 1516/2007 and the F-gas Act, which leak detection methods may not be carried out by a person holding a Category E certificate?
| Visual leak inspection. |
| Measuring leaks using a handheld leak detector. |
| Leak detection using a foaming solution. |
| Leak testing using a fluorescent dye. |
290
Nehéz
According to the current regulation, what sensitivity must a handheld leak detector have?
| 8 g/year. |
| 5 g/year. |
| 10 g/year. |
| 3 g/year. |
291
Közepes
Which category of F-gas certificate (A1, A2, B, C, D, E) authorises the performance of leak tests on refrigeration equipment:
| Categories D and E. |
| Only categories A1 and A2. |
| All except category D. |
| Category E only. |
292
Nehéz
Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?
| At any time. |
| Immediately after the repair. |
| At the next periodic inspection. |
| Between 24 hours and 1 month after the repair. |
293
Nehéz
At what intervals should leak tests be carried out on refrigeration equipment containing more than 500 tonnes of CO₂ equivalent of fluorinated greenhouse gases that does not have a leak detection system installed?
| Once a month. |
| Once every 12 months. |
| Once every 3 months. |
| Once every 6 months. |
294
Közepes
Why is it advisable to subcool the liquid refrigerant?
| This is advisable because it allows a smaller evaporator to be used (lower refrigerant temperature at the evaporator inlet). |
| This is advisable because it allows a smaller condenser to be used (smaller heat exchange surface area). |
| This is advisable because it allows a smaller expansion valve to be used (less superheat at the valve). |
| This is advisable because it ensures that the liquid refrigerant, free of vapour bubbles, enters the expansion valve. |
295
Közepes
What should be done following repairs to a leak in the refrigeration unit of a refrigerated trailer?
| An invoice for the service work carried out must be issued as soon as possible. |
| A visual inspection should be carried out only on bolted and soldered joints. |
| The unit must be charged with an alternative refrigerant, started up, and the refrigerant parameters checked at the service valve located on the liquid receiver. |
| You must enter the details into the equipment log (including the quantities of refrigerant recovered and used) and inform the Operator that an additional leak test must be carried out by a certified person within one month of the repair. |
296
Közepes
Recovery of fluorinated greenhouse gases means:
| The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases. |
| The reuse of fluorinated greenhouse gases following a basic purification process. |
| The collection and storage of fluorinated greenhouse gases originating, for example, from machinery, equipment and containers. |
| The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties. |
297
Közepes
Who is authorised to recover refrigerant from stationary refrigeration equipment:
| The operator. |
| The administrator of the operator’s account. |
| A service technician holding an F-gas certificate in the relevant category. |
| The owner of the installation. |
298
Közepes
Recovered refrigerants must be stored:
| In any pressure vessel that has been officially certified. |
| In any used refrigerant cylinder. |
| In a specially adapted and labelled cylinder fitted with a two-way valve. |
| In a cylinder that previously contained the same type of refrigerant. |
299
Közepes
When should the recovery of fluorinated greenhouse gases be carried out:
| Before the final disposal of equipment and, where applicable, during its servicing and maintenance. |
| Before each leak test of the equipment. |
| Only prior to the final disposal of equipment. |
| Always during servicing and maintenance of equipment. |
300
Közepes
What should be done if the refrigerant recovered from the system is contaminated, e.g. with acid, air or moisture?
| You should attempt to purify the mixture yourself using a dehydrating filter. |
| Such a mixture must be handed over to a specialist authorised company for regeneration or disposal. |
| Add a special contaminant neutraliser to the mixture. |
| Purify the mixture by passing it through a particulate filter and reuse it. |
301
Közepes
What should be done if different types of refrigerants become mixed in a storage cylinder (container)?
| Add a special refrigerant to the mixture. |
| You should attempt to separate the mixture into its individual components. |
| Send this mixture to a specialist authorised company to have it neutralised. |
| The mixture should be purified by passing it through a filter-drain and reused. |
302
Közepes
How does refrigerant recovery using the Push-Pull method work?
| This involves injecting nitrogen from the cylinder into the unit and expelling the liquid refrigerant from the unit. |
| This involves using a suction device (compressor) to ensure that the refrigerant, in liquid form, is transferred into the cylinder. |
| It involves using a recovery unit to draw (pull) the refrigerant vapour from the cylinder and then force it (push) into the low-pressure side of the system. |
| This involves the refrigerant being alternately drawn from the suction side and then from the discharge side of the refrigeration unit (compressor). |
303
Közepes
What are the methods for managing waste refrigerant?
| Regeneration, recovery. |
| Disposal, storage. |
| Recovery, disposal. |
| Recycling, regeneration, disposal. |
304
Közepes
The most advantageous method of managing waste refrigerant is:
| Disposal. |
| Storage. |
| Regeneration. |
| Recycling. |
305
Közepes
The lower the evaporation temperature, ...
| …the greater the density of the refrigerant and the lower the mass flow rate of the refrigerant. |
| ...the greater the density of the refrigerant and the mass flow rate of the flowing refrigerant. |
| ...the lower the density of the refrigerant and the lower the mass of the flowing refrigerant. |
| ...the lower the refrigerant density, and the greater the cooling capacity of the compressor. |
306
Közepes
How should pressure vessels (e.g. refrigerant cylinders) be marked?
| They should bear, amongst other things, information such as: the number of the standard applied to their design, construction and testing; the identification marks of the country of approval and the inspection body; the date of the acceptance test; and the manufacturer’s and operational marks. |
| They should bear only markings relating to weight and capacity. |
| It is irrelevant how pressure vessels should be marked. |
| They should bear the manufacturer’s logo and the date of manufacture. |
307
Közepes
The recovery of refrigerants does not require the use of:
| An electronic leak detector. |
| Hoses with shut-off valves. |
| A refrigerant recovery station. |
| Scales with a measurement range suitable for the size of the cylinder being filled. |
308
Közepes
What functions does the compressor perform in a refrigeration system?
| The compressor creates a vacuum on the suction side of the system |
| The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure. |
| The compressor compresses ambient air and increases the pressure of the refrigerant. |
| The compressor condenses the refrigerant. |
309
Könnyű
What is the compressor’s compression ratio?
| It is the ratio of the discharge pressure to the effective capacity of the compressor (p/Vk). |
| It is the amount of refrigerant that will be compressed in a single compressor cycle relative to the heat capacity. |
| It is the ratio of the discharge pressure to the suction pressure of the compressor (pk/po). |
| It is the ratio of the suction pressure to the discharge pressure of the compressor (po/pk). |
310
Közepes
What is compressor flooding?
| Flooding the compression chamber with liquid refrigerant or oil. |
| Flooding of the compressor due to rainfall. |
| A large amount of liquid refrigerant in the evaporator. |
| Suction of liquid refrigerant into the compressor’s suction line. |
311
Közepes
To what extent do we regulate the compressor motor’s rotational speed when using a frequency converter?
| From approximately 30% to 90% of capacity. |
| Regulating the compressor motor speed is not the same as regulating the cooling capacity. |
| Approximately from 30 to 75 Hz, which corresponds to around 60% to 150% of the cooling capacity. |
| Up to a maximum of 10 per cent. |
312
Könnyű
What is the theoretical displacement of a compressor?
| The displacement capacity of a compressor is expressed by the coefficient of performance (COP) |
| The displacement of a compressor is determined by the dimensions of the cylinder – its volume (cm³) |
| This is the volume of refrigerant that flows through a reciprocating compressor during a single piston cycle. |
| It is the volume of refrigerant delivered by a reciprocating compressor per unit of time, usually referred to by the manufacturer as the displacement. It depends on the compressor’s geometric dimensions and rotational speed. |
313
Közepes
Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?
| Because these types of compressors are sensitive to voltage drops. |
| Because this type of compressor has difficulty starting up if the phase sequence is changed. |
| Because the motor speed would decrease, and consequently the compressor’s capacity. |
| Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors. |
314
Közepes
The cycle of a two-stage vapour-compression refrigeration system should have, in each stage of the system:
| a compression ratio of less than 8. |
| a compression ratio greater than 8. |
| a compression ratio of less than 18. |
| a compression ratio of less than 6 |
315
Közepes
Why is it necessary to seal the shafts in gland-sealed refrigeration compressors?
| Because we need to prevent air from entering the compressor and we need to prevent refrigerant from leaking from the compressor. |
| Because it protects the compressor’s crankshaft bearing. |
| Because it prevents oil leakage. |
| Because it ensures the bearing remains lubricated. |
316
Közepes
When is the refrigerant sufficiently cooled?
| When no vapour bubbles are observed forming in the liquid sight glass. |
| When the liquid distributors are warm. |
| When the evaporator is covered in frost. |
| When the outlet from the condenser is cold. |
317
Közepes
Why should the compressor crankcase be heated?
| Heating prevents the refrigerant from dissolving in the oil. |
| Heating improves the dissolution of the refrigerant in the oil, which is beneficial for its viscosity. |
| Heating keeps the lubricating oil in a liquid state. |
| Heating ensures that the lubricating oil is de-watered. |
318
Könnyű
What is the dead volume of a compressor?
| It is the space between the valve plate and the top of the piston. |
| This is the space between the side surface of the piston and the cylinder. |
| This is the space between the bottom of the piston and the crankshaft cover. |
| It is the space between the valve plate and the bottom dead centre of the piston. |
319
Közepes
What are compressor sets?
| These are sets comprising several compressors connected in any configuration. |
| These are multiple (several) air-cooled condensers. |
| These consist of a larger number (several) of compressors connected in parallel and mounted on a common frame. |
| These are units consisting of two-stage compressors. |
320
Közepes
What are the advantages of compressor units?
| The ability to adjust the cooling capacity as required. |
| Space-saving and lower energy consumption. |
| These are inexpensive and easy-to-install units. |
| Easy modification of the system. |
321
Közepes
What do we mean by the ‘application range’ of a compressor?
| By this term, we mean the following parameters: the evaporation and condensation temperatures (to and tk), or the pressure values that determine the compressor’s application. |
| By this term, we mean the following parameters: compressor capacity, type of refrigerant, and the compressor’s geometric dimensions. |
| By this term, we mean that the compressor’s operating range is determined by the evaporation temperature ‘to’ during operation. |
| By this term, we mean that the compressor’s application range is determined by the evaporation temperature ‘to’ at a given ambient temperature. |
322
Közepes
What are the basic functions of oil in a compressor?
| The oil seals the gap between the piston and the cylinder. |
| The oil seals any leaks that develop in the system. |
| The oil lubricates both the bearings and the sliding surfaces of the compressor components, and cools the compressor by transferring the heat generated during compression to the compressor’s outer casing. |
| The oil absorbs moisture from the refrigerant that enters the compressor. |
323
Közepes
What are the most effective ways of regulating the compressor’s cooling capacity?
| Using an expansion valve. |
| By means of pressure control valves. |
| By changing the compressor’s displacement, by varying the rotational speed, or by deactivating individual cylinders. |
| By partially covering the evaporator to reduce the heat exchange surface area. |
324
Közepes
What does compressor bypass control involve?
| Hot, high-pressure refrigerant vapour is drawn in on the suction side of the compressor. |
| Refrigerant in the form of cooled, high-pressure vapour is introduced into the suction line. |
| The bypass control is not used to regulate the compressor. |
| High-pressure liquid refrigerant is injected on the suction side of the compressor. |
325
Közepes
What is the fundamental difference between hermetic and semi-hermetic compressors?
| The housing of a hermetic compressor and the compressor itself form a single unit. |
| Both types of compressors are disassemblable, and the difference lies in their varying capacities. |
| The casing of semi-hermetic compressors can be dismantled, whereas the casing of hermetic compressors cannot be dismantled. |
| Semi-hermetic compressors are characterised by the quiet operation of the entire unit. |
326
Közepes
How does a scroll compressor work?
| It is a type of piston-type device. |
| A scroll compressor is also known as a turbo compressor. |
| It uses two screws to compress the refrigerant. |
| It is a device fitted with two spirals. It is a type of positive displacement (volumetric) compressor in which compression takes place through the interaction of the two spirals. |
327
Közepes
What physical process takes place in the evaporator?
| The liquid refrigerant evaporates and a small amount of it becomes superheated. |
| It causes the refrigerant flowing through it to condense. |
| It cools the refrigerant flowing through it. |
| The medium flowing through the evaporator (glycol, water) evaporates, whilst the refrigerant condenses. |
328
Közepes
What is the purpose of regulating the compressor’s capacity?
| It ensures adequate lubrication of the compressor. |
| It allows the cooling capacity to be adjusted to meet requirements. |
| Capacity control protects the compressor from low thermal loads. |
| It ensures that the cooling capacity is adjusted based on condensing temperatures. |
329
Közepes
Why is inverter speed control suitable for refrigeration compressors?
| Inverter speed control can be used with any type of compressor to ensure adequate lubrication. |
| By reducing the speed of the refrigeration compressor motor, inverter speed control improves the return oil flow to the compressor. |
| Inverter speed control enables continuous, smooth regulation of cooling capacity. |
| Inverter speed control reduces energy consumption only under natural conditions. |
330
Közepes
Does the suction gas temperature affect the cooling capacity of the compressor?
| It does, but only if the gas is deeply cooled. |
| Temperature has no effect on the compressor’s cooling capacity. |
| It has a significant effect on performance. |
| It does, but only for reciprocating compressors. |
331
Közepes
In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?
| No. |
| Only scroll compressors. |
| Yes. |
| Only screw compressors. |
332
Közepes
What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?
| This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off. |
| This compressor condenses the refrigerant whilst the vehicle is in motion. |
| The compressor compresses ambient air and increases the pressure of the refrigerant. |
| This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running. |
333
Közepes
Which natural fluids absorb heat from the refrigerant in the condenser?
| Water and an antifreeze mixture. |
| Air and CO2. |
| Water or air. |
| Ammonia |
334
Közepes
What is the function of the condenser in refrigeration systems?
| Heat released in the regenerative heat exchanger is absorbed by the condenser. |
| The heat absorbed in the evaporator and transferred during the compression process is then released into the environment via the condenser. |
| Heat from the compressor is then released into the environment via the condenser. |
| The heat absorbed in the evaporator is then released into the environment via the condenser |
335
Közepes
If the condensation temperature is higher than the critical point temperature of the refrigerant, condensation:
| will occur provided a specially designed condenser is used. |
| will always occur regardless of the temperature. |
| will not occur. |
| temperature has no effect on condensation. |
336
Közepes
How does the subcooling of the refrigerant take place within a refrigeration system?
| Subcooling using high-pressure hot vapour. |
| Subcooling of the refrigerant using oil (dissolving the refrigerant in oil). |
| Subcooling of the liquid refrigerant in the final section of the condenser. |
| Subcooling using an additional heat exchanger and liquid nitrogen. |
337
Közepes
What is the purpose of controlling the condenser fan speed?
| Condenser fan speed control ensures that the condensing pressure is maintained at the correct level. |
| Condenser fan speed control reduces energy efficiency. |
| Dispersion of the refrigerant in the event of a system leak. |
| Condenser fan speed control safeguards against the maximum permissible condensing pressure. |